Genkit : Produce your own Electricity
HOME ABOUT US CONTACT US

Batteries ~ Long life, deep-cycle ~ create and store electricity

batteryrange1.jpg: Battery range

Batteries can be used for large-scale power requirements

Batteries are a part of our everyday life. We use them in our cars, cell phones, PC's, laptops, MP3 players and more. People are now starting to use more sophisticated long life batteries to create and store electricity, for use in their homes, on boats, and for back-up and remote power.

How batteries work

A battery is, by definition, an electrochemical device that converts chemical energy into electricity, by a galvanic cell. A galvanic cell is a fairly simple device consisting of two electrodes of different metals or metal compounds (an anode and a cathode) and an electrolyte (usually acid, but some are alkaline) solution. As chemicals in the battery change, electrical energy is stored or released.

Deep cycle batteries for electricity supply

Deep-cycle, long life batteries are designed to be discharged down as much as 80% time after time, and have much thicker plates. The major difference between a true deep-cycle battery and others, is that the plates are SOLID Lead plates - not sponge. In the case of battery use for solar power, a charge controller is used, which is a regulator that sits between the solar panels and the batteries. Regulators for solar power are designed to keep the batteries charged at peak without overcharging, which helps to extend the battery life and charge.



Genkit Batteries ~ GEN OPzS Series Vented batteries

Application:

  • Remote area power supply systems comprising:
    Hydro-Solar-Wind
  • Telecommunication equipment, as back-up.
  • Remote Area radio and cell phone relay stations.
  • Back-up for power station controls.
  • Large UPS stored energy.

Features:

  • Long life warranties and depending on the installation configuration and control, up to 10 years.
  • High cycle life.
  • No positive plate growth.
  • These withstand higher temperatures than calcium alloys.
  • Tank formed plates.
  • Watering intervals (6 months to 3 years) – this is dependant on the number of charge and discharge cycles experienced per annum and the related DOD (depths of discharge) experienced.
    NB: Only use di-ionised distilled water to top up these cells.
    No premature failures due to antimonal poisoning.

Brief Description:
These cells are distinguished by their lead selenium tubular plate design and high tolerance to cycling, leading to providing the best possible compromise in lead acid plate technology. By utilising a proportion of selenium in the grid alloy, a dense fine grain structure is produced.

This alloy is extremely corrosion resistant and virtually eliminates inter-granular corrosion, being one of the most common causes of cell failure.

These cells combine the advantages of both lead calcium and lead antimony cells, whilst exhibiting none of the disadvantages.

GEN OPzS Series ~ Basic Specifications

Type
Rated V.V
Rated C10 Ah
Max. outside six mm
L x W x H x TH
Cell weight kg
Dry x Wet x Electrolyte
Nos. of terminals of same polarity
6OPzS 50 12 50 272x205x335x390 25.5x37.0x11.5 1
6OPzS 100 12 100 272x205x335x390 39.0x48.0x9.0 1
6OPzS150 12 150 380x205x335x390 54.0x68.0x14.0 1
3OPzS200 6 200 272x205x335x390 35.0x45.5x10.5 1
3OPzS250 6 250 380x205x335x390 45.0x59.0x14.0 1
3OPzS300 6 300 380x205x335x390 51.0x65.0x14.0 1
OPzS100
2 100 103x206x354x409 7.6x12.6x5.0 1
OPzS150
2 150 103x206x354x409 10.8x15.3x4.5 1
OPzS200
2 200 103x206x354x409 13.2x17.2x4.0 1
OPzS250
2 250 124x206x354x409 16.2x20.8x4.6 1
OPzS300
2 300 145x206x354x409 19.2x24.3x5.1 1
OPzS350
2 350 124x206x470x525 19.4x26.9x7.5 1
OPzS420
2 420 145x206x470x525 23.4x31.5x8.1 1
OPzS490
2 500 166x206x470x525 27.4x36.1x87 1
OPzS600 2 600 145x206x645x700 33.9x44.8x10.9 1
OPzS800 2 800 191x210x645x700 45.3x61.5x16.0 2
OPzS1000 2 1000 233x210x645x700 55.5x74.6x19.1 2
OPzS1200 2 1200 275x210x645x700 65.8x88.0x22.2 2
OPzS1500 2 1500 275x210x795x850 87.0x114.3x27.3 2
OPzS1750 2 1750 399x214x771x826 105.0x140.2x35.2 3
OPzS1875 2 1875 399x214x771x826 113.0x158.0x45.0 3
OPzS2000 2 2000 399x214x771x826 123.0x166.0x43.0 3
OPzS2250 2 2250 487x212x771x826 142.0x195.0x53.0 4
OPzS2500 2 2500 487x212x771x826 152.0x204.0x52.0 4
OPzS3000 2 3000 576x212x771x826 179.0x242.0x63.0 4


Genergiser Battery Operation Guide